Proof it holds full load.
A generator that starts is not the same as a generator that carries your site. A load bank test runs it up to full rated load and records what it does.
What a load bank test is.
What we do
We connect a load bank to the generator and step the load up to full rated load, holding each step.
What we record
Load, voltage, frequency and coolant temperature at each step, and how long it held.
What it finds
Faults that only show when the generator is working hard: overheating, fuel problems, voltage or frequency that drops away under load.
What you get
A written report with the readings, the result, and anything to fix before it becomes a breakdown.
How often
Every 12 months on our standby and prime power plans. You can also add one to a one-off service.
The work, then the proof.
On a service
- Engine oil and oil filter changed
- Fuel filter and air filter replaced
- Coolant, belts and hoses checked
- Start battery tested, and replaced when it's due
- Controller, alarms and safety shutdowns checked
On a test
- Load bank test up to full rated load
- Automatic transfer switch tested
- Blackstart test: we drop the mains and watch it take over
- Thermal imaging of switchboards and connections
- Generator
- 100 kVA diesel, standby
- Test
- Load bank, stepped to full rated load
| Load | kW | Min | Hz | Coolant |
|---|---|---|---|---|
| 25% | 20 | 15 | 50.1 | 74°C |
| 50% | 40 | 15 | 50.0 | 80°C |
| 75% | 60 | 30 | 50.0 | 84°C |
| 100% | 80 | 60 | 49.9 | 88°C |
Every visit ends with a written report: what we did, what the readings were, and anything to fix before it becomes a breakdown.
The rest of the system.
The generator is one part. These tests cover what sits between it and your site.
Transfer switch test
We test the automatic transfer switch, the part that hands your site over to the generator.
Blackstart test
We drop the mains and watch the generator take over.
Thermal imaging
Thermal imaging of switchboards and connections.